How-to guidePublished

Rack-Mount a Juniper EX4300 on Two or Four Posts

Models covered: EX4300, EX4300-24P, EX4300-48T, EX4300-48P, EX4300-48MP, EX-4PST-RMK

Tools and parts needed

  • Phillips (+) screwdriver, number 2
  • 2 mounting brackets and 8 mounting screws (in the switch's accessory box)
  • Screws to secure the chassis to the rack (not provided)
  • For four posts or a recessed mount: the four-post rack-mount kit (EX-4PST-RMK)
  • Cover panels for uplink module and power supply slots (provided)

The maker's warnings

  • One person must lift the switch while another secures it to the rack.[S1]
  • When mounting several units, start at the bottom of the rack and put the heaviest unit lowest.[S1]
  • Place the rack in its permanent location and secure it to the building before mounting anything.[S1]
  • In an earthquake-prone area, secure the rack to the floor.[S2]

Steps

  1. Step 1: Two posts: fit the brackets

    With the switch on a flat, stable surface, align the mounting brackets along the front, rear or center of the side panels. On EX4300 models other than the EX4300-48MP, align them along the front of the side panel for a front mount.[S1]

  2. Step 2: Two posts: EX4300-48MP bracket offset

    To front-mount an EX4300-48MP, align the brackets 17.5 mm offset from the front panel.[S1]

  3. Step 3: Two posts: screw on the brackets

    Align the bottom bracket holes with the holes in the side panels, insert the mounting screws, then fill and tighten every remaining hole with the Phillips screwdriver.[S1]

  4. Step 4: Two posts: lift and secure

    One person lifts the switch into the rack and aligns the bottom bracket hole with a hole in each rail, keeping the chassis level; a second person secures it with the rack screws and tightens them.[S1]

  5. Step 5: Four posts: attach the side rails

    Align the side mounting-rails with the side panels, matching the two rear holes, and fasten them with the 4x6-mm Phillips flat-head screws in all six holes. For a recessed mount, first swap the short front brackets on the rails for the long ones.[S1]

  6. Step 6: Four posts: secure the front

    One person lifts the switch and aligns it with the front posts, level; a second person secures the front to the rack with screws for your rack.[S1]

  7. Step 7: Four posts: fit the rear blades

    Slide the rear mounting-blades into the side mounting-rails and screw them to the rear posts.[S1]

  8. Step 8: Check it is level and cover empty slots

    Confirm the chassis is level by checking that the screws on each side line up, and fit cover panels in the unused uplink module and power supply slots.[S1]

A Juniper EX4300 stands 1.72 in. (4.37 cm) tall, and Juniper lets you mount it four ways: on two posts with the brackets in the box, on four posts with the separately orderable four-post rack-mount kit, recessed 2 in. from the rack front, or on a wall. This guide covers the two rack methods, which fit any 19-in. rack whose holes are spaced at 1U (1.75 in. or 4.45 cm).

Size and weight

ItemJuniper's figure
Chassis height1.72 in. (4.37 cm)
Chassis width17.36 in. (44.1 cm); 19 in. (48.2 cm) across the front-mounting brackets
Depth with power supply (models other than the EX4300-32F and EX4300-48MP)17.51 in. (44.47 cm), or 18 in. (45.73 cm) with an uplink module
Weight, chassis only (except EX4300-48MP)13 lb (5.9 kg) with no power supply and no fan module
350 W or 715 W AC power supply2.4 lb (1.1 kg) each
Fan module0.33 lb (0.15 kg)

The weight is easy for one person, but Juniper still asks for two: one person must be available to lift the switch while another secures it to the rack.

Measure the rack before you start

The rack must meet the size and strength standards of a 19-in. rack as defined by the ECIA, and be secured to the building structure. For a four-post mount, depth matters because the rear mounting-blade has an opening for the protective earthing terminal. Juniper's mounting topic asks for a rack 27.5 in. (70 cm) through 30.5 in. (77.5 cm) deep for a flush mount, and 29.5 in. (75 cm) through 32.5 in. (82.5 cm) deep for a mount 2 in. recessed. Its site requirements topic states the post spacing for the four-post kit: a minimum of 24 in. (60.96 cm) between front and rear posts, extendable up to 31.5 in. (80 cm), for a flush mount, and a minimum of 26 in. (66.04 cm) for a recessed mount with the EX-4PST-RMK. Check your rack against both sets of figures.

In a cabinet, the minimum cabinet size is 27.7 in. (70.35 cm) between the front door and the rear wall, with at least 6 in. between each door or wall and the switch.

Inside a cabinet, the hot air exhaust of the chassis must exit the cabinet without recirculating into the device, and Juniper says an open cabinet that draws exhaust out through the top gives the best airflow through the chassis. Where the cabinet has a top or doors, perforations in them help remove the hot air, and cables should be routed and secured to minimize the blockage of airflow.

Clearance around the switch

  • Airflow: leave at least 6 in. (15.2 cm) clearance in front of and behind the chassis.
  • Grounding: leave at least 6 in. (15.2 cm) clearance on the left of the chassis for installing the grounding lug.
  • Service: leave at least 24 in. (61 cm) clearance in front of and behind the switch for people to remove and install hardware components.
  • Neighbors: make sure the exhaust from other equipment does not blow into the intake vents of the chassis.

When to recess the switch

Recessing the switch 2 in. into the rack solves two common problems. One is a cabinet whose doors do not close completely unless the switch is recessed. The other is an uplink module with transceivers installed, because the transceivers in the uplink module ports protrude from the front of the switch. The recess brackets come only in the four-post kit, but you can use them on two-post or four-post racks.

Before the switch leaves the carton

Juniper's advice is to leave the switch in its carton until you are ready to begin installation, since that is where it is best protected. Move the carton to a staging area as close to the installation site as possible, with the arrows pointing up, then open the top flaps and pull out the packing material. Check the parts against the packing list, and keep the carton and packing materials in case you need to move or ship the switch later.

What is in the box, and what is not

A standard EX4300 ships with 2 mounting brackets, 8 mounting screws and 4 rubber feet, but you must provide the appropriate mounting screws for the rack itself. The four-post kit adds a pair of side mounting-rails, a pair of rear mounting-blades, flush or 2-in.-recess front-mounting brackets, and 6 flat-head 4-40 and 12 flat-head 4x6-mm Phillips screws. The models ending in -S ship without power supplies or fan modules, so order those before the install day.

In stock at Townsend

We have the EX-4PST-RMK in stock for anyone moving an EX4300 onto four posts or recessing it. The EX4300-24P, the EX4300-48T and the EX4300-48MP are in stock too. See the EX4300 shelf and the EX accessories shelf for switches, kits and modules.

Sources

Checked against the maker's documents on .

  1. S1Unpacking and Mounting the EX4300 SwitchJuniper Networks · Document: EX4300 Switch Hardware Guide · Revision: Topic page dated 2025-06-29 · Section: Unpacking an EX4300 Switch; Parts Inventory; Mounting an EX4300 Switch on Two Posts, on Four Posts, in a Recessed Position · June 29, 2025

  2. S2EX4300 Site Guidelines and RequirementsJuniper Networks · Document: EX4300 Switch Hardware Guide · Revision: Topic page dated 2025-06-29 · Section: Rack Requirements; Cabinet Requirements; Clearance Requirements for Airflow and Hardware Maintenance · June 29, 2025

  3. S3EX4300 System OverviewJuniper Networks · Document: EX4300 Switch Hardware Guide · Revision: Topic page dated 2025-07-28 · Section: Chassis Physical Specifications for EX4300 Switches; Field-Replaceable Units in EX4300 Switches · July 28, 2025

In stock now

EX-4PST-RMK Juniper Rack Kit, Refurbished

EX-4PST-RMK

EX-4PST-RMK Juniper Rack Kit, Refurbished

In stock

$2,130Ships same day
EX4300-24P Juniper Switch, Front-to-Back, Refurbished, 24x 1GbE PoE+ RJ45 and 4x 40GbE QSFP+

EX4300-24P

EX4300-24P Juniper Switch, Front-to-Back, Refurbished, 24x 1GbE PoE+ RJ45 and 4x 40GbE QSFP+

In stock

$590Ships same day
EX4300-48T Juniper Switch, Front-to-Back, Refurbished, 48x 1GbE RJ45 and 4x 40GbE QSFP+

EX4300-48T

EX4300-48T Juniper Switch, Front-to-Back, Refurbished, 48x 1GbE RJ45 and 4x 40GbE QSFP+

In stock

$145Ships same day
EX4300-48MP Juniper Switch, Front-to-Back, 48x 1GbE PoE++ RJ45 (24 × 10GbE) and 4x 40GbE QSFP+