A Juniper EX4300 stands 1.72 in. (4.37 cm) tall, and Juniper lets you mount it four ways: on two posts with the brackets in the box, on four posts with the separately orderable four-post rack-mount kit, recessed 2 in. from the rack front, or on a wall. This guide covers the two rack methods, which fit any 19-in. rack whose holes are spaced at 1U (1.75 in. or 4.45 cm).
Size and weight
| Item | Juniper's figure |
|---|---|
| Chassis height | 1.72 in. (4.37 cm) |
| Chassis width | 17.36 in. (44.1 cm); 19 in. (48.2 cm) across the front-mounting brackets |
| Depth with power supply (models other than the EX4300-32F and EX4300-48MP) | 17.51 in. (44.47 cm), or 18 in. (45.73 cm) with an uplink module |
| Weight, chassis only (except EX4300-48MP) | 13 lb (5.9 kg) with no power supply and no fan module |
| 350 W or 715 W AC power supply | 2.4 lb (1.1 kg) each |
| Fan module | 0.33 lb (0.15 kg) |
The weight is easy for one person, but Juniper still asks for two: one person must be available to lift the switch while another secures it to the rack.
Measure the rack before you start
The rack must meet the size and strength standards of a 19-in. rack as defined by the ECIA, and be secured to the building structure. For a four-post mount, depth matters because the rear mounting-blade has an opening for the protective earthing terminal. Juniper's mounting topic asks for a rack 27.5 in. (70 cm) through 30.5 in. (77.5 cm) deep for a flush mount, and 29.5 in. (75 cm) through 32.5 in. (82.5 cm) deep for a mount 2 in. recessed. Its site requirements topic states the post spacing for the four-post kit: a minimum of 24 in. (60.96 cm) between front and rear posts, extendable up to 31.5 in. (80 cm), for a flush mount, and a minimum of 26 in. (66.04 cm) for a recessed mount with the EX-4PST-RMK. Check your rack against both sets of figures.
In a cabinet, the minimum cabinet size is 27.7 in. (70.35 cm) between the front door and the rear wall, with at least 6 in. between each door or wall and the switch.
Inside a cabinet, the hot air exhaust of the chassis must exit the cabinet without recirculating into the device, and Juniper says an open cabinet that draws exhaust out through the top gives the best airflow through the chassis. Where the cabinet has a top or doors, perforations in them help remove the hot air, and cables should be routed and secured to minimize the blockage of airflow.
Clearance around the switch
- Airflow: leave at least 6 in. (15.2 cm) clearance in front of and behind the chassis.
- Grounding: leave at least 6 in. (15.2 cm) clearance on the left of the chassis for installing the grounding lug.
- Service: leave at least 24 in. (61 cm) clearance in front of and behind the switch for people to remove and install hardware components.
- Neighbors: make sure the exhaust from other equipment does not blow into the intake vents of the chassis.
When to recess the switch
Recessing the switch 2 in. into the rack solves two common problems. One is a cabinet whose doors do not close completely unless the switch is recessed. The other is an uplink module with transceivers installed, because the transceivers in the uplink module ports protrude from the front of the switch. The recess brackets come only in the four-post kit, but you can use them on two-post or four-post racks.
Before the switch leaves the carton
Juniper's advice is to leave the switch in its carton until you are ready to begin installation, since that is where it is best protected. Move the carton to a staging area as close to the installation site as possible, with the arrows pointing up, then open the top flaps and pull out the packing material. Check the parts against the packing list, and keep the carton and packing materials in case you need to move or ship the switch later.
What is in the box, and what is not
A standard EX4300 ships with 2 mounting brackets, 8 mounting screws and 4 rubber feet, but you must provide the appropriate mounting screws for the rack itself. The four-post kit adds a pair of side mounting-rails, a pair of rear mounting-blades, flush or 2-in.-recess front-mounting brackets, and 6 flat-head 4-40 and 12 flat-head 4x6-mm Phillips screws. The models ending in -S ship without power supplies or fan modules, so order those before the install day.