This guide covers the parts of a Juniper MX480 router you are most likely to swap yourself: an AC or DC power supply, the fan tray and the air filter. Every figure and instruction here comes from Juniper's MX480 Universal Routing Platform Hardware Guide, and the numbered steps on this page follow Juniper's own order.
What you can swap with the router running
Juniper splits the MX480's replaceable parts into two groups. A hot-removable and hot-insertable part can come out with the router powered on and still routing: Juniper says you can remove and replace these components without powering off the router or disrupting the routing functions. The air filter, the fan tray and the AC, DC, and HVDC/HVAC power supplies (if redundant) are all in that group.
The words that matter are if redundant. Juniper's warning about a nonredundant configuration, listed above, is the reason: before you pull a supply, count what is installed against what your power configuration needs, as set out in the next section.
How many power supplies an MX480 needs
The MX480 takes up to four power supplies, located horizontally at the rear of the chassis in slots PEM0 through PEM3 (left to right). How many must be running depends on the AC feed. On low-line (110 V) power, the low-line configuration requires three power supplies and the fourth power supply provides redundancy. On high-line (220 V) power, two power supplies carry the full load, and in the two-PEM high-line configuration, either slots PEM0 and PEM1 or slots PEM2 and PEM3 are used. So a router on high-line power with four supplies can lose one for a swap, and a low-line router needs its fourth supply in place before you take any out.
Juniper publishes two families of AC supply for the chassis, normal capacity and high capacity, with these limits:
| AC supply | Redundancy, low line | Redundancy, high line | Maximum output per supply | Maximum output per system |
|---|---|---|---|---|
| Normal capacity | 3+1 | 2+2 | 1027 W low line, 1590 W high line | 3081 W low line, 6400 W high line |
| High capacity | 3+1 | 2+2 | 1167 W low line, 2050 W high line | 3501 W low line, 4100 W high line |
Keep one kind of supply in the chassis. Juniper allows mixing high-capacity and normal-capacity power supplies only during the PEM upgrade process, and does not recommend it in any other case. AC and DC supplies never share a chassis, because mixing them may damage it. All supplies should have the same feed setting.
Breakers, cords and grounding
Each AC supply has a single AC appliance inlet located on the power supply that requires a dedicated AC power feed. For the standard supplies Juniper recommends a customer site circuit breaker rated for 15 A (250 VAC) minimum for each AC power supply, or as required by local code. For high-capacity supplies, each inlet requires a dedicated AC power feed and a dedicated 16.0 A @ 100 VAC or 16.0 A @ 200 VAC circuit breaker, or as required by local code.
Juniper's detachable cords are each approximately 8 ft (2.5 m) long, and the C19 appliance coupler end of the cord inserts into the AC appliance inlet coupler, type C20 (right angle). The chassis also has a separate protective earthing terminal (sized for UNC 1/4-20 ground lugs), and Juniper says it must be permanently connected to earth.
If your MX480 runs on DC
The steps on this page are for AC supplies; a DC supply comes out and goes in the same way but is wired to terminal studs, and Juniper adds rules of its own. With the DC breaker off and taped as the warning above says, Juniper also has you make sure the voltage across the cable leads is 0 V before you touch them. Each lug goes on with the flat washer, then the split washer, then the nut, tightened to between 23 lb-in. (2.6 Nm) and 25 lb-in. (2.8 Nm) with a 7/16-in. [11 mm] torque-controlled driver or socket wrench. The studs themselves are rated to a maximum of 36 lb-in. (4.0 Nm), and too much torque damages them.
Polarity is yours to get right: the positive (+) lead goes to the RTN (return) terminal, and there is no standard color coding for DC power cables. For A/B redundancy, the supplies in PEM0 and PEM1 take feed A and the supplies in PEM2 and PEM3 take feed B. A healthy DC supply shows the PWR OK, BRKR ON, and INPUT OK LEDs light green steadily, and an SCB must be present for the PWR OK LED to go on.
Reading the AC supply LEDs
Each AC power supply faceplate contains three LEDs, and a power supply failure also triggers the red alarm LED on the craft interface.
| LED | What it means |
|---|---|
| AC OK, green | AC power input voltage is within 78 to 264 VAC; off means the input is below 78 VAC |
| DC OK, green | On when the supply's DC outputs are within the normal operating ranges |
| PS FAIL, red | On when the power supply is not functioning normally and its output voltage is out of regulation limits |
If PS FAIL lights, Juniper's advice is to check AC OK and DC OK LEDs for more information: by the table above, a dark AC OK means the input voltage is low, and a dark DC OK with AC OK lit means the supply's own outputs are out of range.
The cooling system and the air filter schedule
The router has one fan tray and one air filter that install vertically in the rear of the router, and the fan tray contains six fans. Air comes in at the side of the chassis next to the air filter and leaves through the fan tray out the other side, while the power supplies draw their air from the front above the craft interface.
If a fan fails, the host subsystem adjusts the speed of the remaining fans to maintain proper cooling, and a red alarm is triggered when a fan fails. The air filter is on a calendar: Juniper says you must replace the filter every 6 months. Spare filters age on the shelf too; the shelf life of polyurethane filter varies from two years to five years depending on the storage conditions.
Dense line cards need the better tray. Juniper says the MX Series high-capacity fan trays satisfy cooling requirements for high-density DPCs and MPCs, and must be upgraded for proper cooling. The high-capacity tray is the FFANTRAY-MX480-HC, which Juniper names alongside the 2520W AC power supply, PWR-MX480-2520-AC, and the 2400W DC power supply, PWR-MX480-2400-DC. When you move to enhanced supplies, Juniper's rule is to always upgrade power supplies in adjacent slots.
In stock at Townsend
We have the PWR-MX480-2520-AC-S AC supply and the PWR-MX480-2400-DC DC supply in stock, along with an MX480 chassis for anyone building a spare. The MX480 shelf gathers the MX480 parts on our site, and the wider Juniper MX collection holds the line cards, Routing Engines and control boards for the other MX chassis.