Replace a Juniper MX480 Power Supply, Fan Tray or Air Filter

Models covered: MX480, PWR-MX480-2520-AC, PWR-MX480-2400-DC, FFANTRAY-MX480-HC

Tools and parts needed

  • Electrostatic discharge (ESD) grounding wrist strap
  • Phillips (+) screwdrivers, numbers 1 and 2 (fan tray and air filter)
  • 7/16-in. (11 mm) nut driver or socket wrench (DC supplies)
  • Blank panels (if component is not reinstalled)
  • Plastic cable ties for the power cord

The maker's warnings

  • Each power supply slot must hold either a power supply or a blank panel. If you remove a supply, install a replacement or a blank panel shortly after, or the running supplies can overheat and shut down.[S1]
  • After powering off a power supply, wait at least 60 seconds before turning it back on.[S1]
  • On a router without redundant supplies, removing one might shut the router down.[S3]
  • Do not mix AC and DC power supplies on an MX480 router.[S2]
  • Keep tools and fingers away from the fans as the tray comes out. The fans might still be spinning.[S4]
  • Install the replacement fan tray immediately after removing the old one, to prevent overheating.[S4]
  • Do not run the router for more than a few minutes without the air filter in place. The fans can pull small bits of wire or other materials into the chassis.[S4]
  • Before any DC power work, switch off the circuit breaker that serves the DC circuit and tape its handle in the off position.[S1]

Steps

  1. Step 1: Switch off the feed for the supply you are removing

    Switch off the dedicated customer site circuit breaker for the power supply, and remove the power cord from the AC power source.[S1]

  2. Step 2: Ground yourself

    Attach an ESD grounding strap to your bare wrist, and connect the other end of the strap to an ESD grounding point.[S1]

  3. Step 3: Turn the supply off and unplug it

    Move the AC input switch next to the appliance inlet on the power supply to the off (O) position, then remove the power cord from the power supply.[S1]

  4. Step 4: Pull the old supply

    Unscrew the captive screws on the bottom edge of the power supply, then pull the power supply straight out of the chassis.[S1]

  5. Step 5: Seat the new supply

    With its AC input switch at off, use both hands to slide the power supply straight into the chassis until the power supply is fully seated in the chassis slot. The faceplate should be flush with any adjacent power supply faceplate or blank.[S1]

  6. Step 6: Secure it and connect the cord

    Tighten both captive screws at the bottom of the power supply, attach the power cord, and route it along the cable restraint toward the left or right corner of the chassis, using plastic cable ties if needed.[S1]

  7. Step 7: Power it on and read the LEDs

    Attach the cord to the AC power source, switch on the site circuit breaker, and move the AC input switch to on. A good supply shows the AC OK and DC OK LEDs lit steadily and the PS FAIL LED dark.[S1]

  8. Step 8: Pull the fan tray

    Loosen the captive screws on the fan tray faceplate, grasp the handle and pull the tray out approximately 1 to 3 inches, press the latch on the inside of the tray to release it, then support it with one hand under it and pull it completely out.[S4]

  9. Step 9: Install the replacement fan tray

    Grasp the handle and insert the tray straight into the chassis, using the this side up label on its top surface for orientation, then tighten the captive screws on the faceplate.[S4]

  10. Step 10: Remove the old air filter

    Loosen the captive screws on the air filter cover, remove the cover, and slide the air filter out of the chassis.[S4]

  11. Step 11: Install the new air filter

    Find the up arrow so the filter is right side up, slide it straight in until it stops, align the cover's captive screws with the mounting holes, and tighten them.[S4]

  12. Step 12: Check the router from the CLI

    Run show chassis alarms to see any power alarm still standing, and show chassis environment to confirm every fan reports OK.[S1]

This guide covers the parts of a Juniper MX480 router you are most likely to swap yourself: an AC or DC power supply, the fan tray and the air filter. Every figure and instruction here comes from Juniper's MX480 Universal Routing Platform Hardware Guide, and the numbered steps on this page follow Juniper's own order.

What you can swap with the router running

Juniper splits the MX480's replaceable parts into two groups. A hot-removable and hot-insertable part can come out with the router powered on and still routing: Juniper says you can remove and replace these components without powering off the router or disrupting the routing functions. The air filter, the fan tray and the AC, DC, and HVDC/HVAC power supplies (if redundant) are all in that group.

The words that matter are if redundant. Juniper's warning about a nonredundant configuration, listed above, is the reason: before you pull a supply, count what is installed against what your power configuration needs, as set out in the next section.

How many power supplies an MX480 needs

The MX480 takes up to four power supplies, located horizontally at the rear of the chassis in slots PEM0 through PEM3 (left to right). How many must be running depends on the AC feed. On low-line (110 V) power, the low-line configuration requires three power supplies and the fourth power supply provides redundancy. On high-line (220 V) power, two power supplies carry the full load, and in the two-PEM high-line configuration, either slots PEM0 and PEM1 or slots PEM2 and PEM3 are used. So a router on high-line power with four supplies can lose one for a swap, and a low-line router needs its fourth supply in place before you take any out.

Juniper publishes two families of AC supply for the chassis, normal capacity and high capacity, with these limits:

AC supplyRedundancy, low lineRedundancy, high lineMaximum output per supplyMaximum output per system
Normal capacity3+12+21027 W low line, 1590 W high line3081 W low line, 6400 W high line
High capacity3+12+21167 W low line, 2050 W high line3501 W low line, 4100 W high line

Keep one kind of supply in the chassis. Juniper allows mixing high-capacity and normal-capacity power supplies only during the PEM upgrade process, and does not recommend it in any other case. AC and DC supplies never share a chassis, because mixing them may damage it. All supplies should have the same feed setting.

Breakers, cords and grounding

Each AC supply has a single AC appliance inlet located on the power supply that requires a dedicated AC power feed. For the standard supplies Juniper recommends a customer site circuit breaker rated for 15 A (250 VAC) minimum for each AC power supply, or as required by local code. For high-capacity supplies, each inlet requires a dedicated AC power feed and a dedicated 16.0 A @ 100 VAC or 16.0 A @ 200 VAC circuit breaker, or as required by local code.

Juniper's detachable cords are each approximately 8 ft (2.5 m) long, and the C19 appliance coupler end of the cord inserts into the AC appliance inlet coupler, type C20 (right angle). The chassis also has a separate protective earthing terminal (sized for UNC 1/4-20 ground lugs), and Juniper says it must be permanently connected to earth.

If your MX480 runs on DC

The steps on this page are for AC supplies; a DC supply comes out and goes in the same way but is wired to terminal studs, and Juniper adds rules of its own. With the DC breaker off and taped as the warning above says, Juniper also has you make sure the voltage across the cable leads is 0 V before you touch them. Each lug goes on with the flat washer, then the split washer, then the nut, tightened to between 23 lb-in. (2.6 Nm) and 25 lb-in. (2.8 Nm) with a 7/16-in. [11 mm] torque-controlled driver or socket wrench. The studs themselves are rated to a maximum of 36 lb-in. (4.0 Nm), and too much torque damages them.

Polarity is yours to get right: the positive (+) lead goes to the RTN (return) terminal, and there is no standard color coding for DC power cables. For A/B redundancy, the supplies in PEM0 and PEM1 take feed A and the supplies in PEM2 and PEM3 take feed B. A healthy DC supply shows the PWR OK, BRKR ON, and INPUT OK LEDs light green steadily, and an SCB must be present for the PWR OK LED to go on.

Reading the AC supply LEDs

Each AC power supply faceplate contains three LEDs, and a power supply failure also triggers the red alarm LED on the craft interface.

LEDWhat it means
AC OK, greenAC power input voltage is within 78 to 264 VAC; off means the input is below 78 VAC
DC OK, greenOn when the supply's DC outputs are within the normal operating ranges
PS FAIL, redOn when the power supply is not functioning normally and its output voltage is out of regulation limits

If PS FAIL lights, Juniper's advice is to check AC OK and DC OK LEDs for more information: by the table above, a dark AC OK means the input voltage is low, and a dark DC OK with AC OK lit means the supply's own outputs are out of range.

The cooling system and the air filter schedule

The router has one fan tray and one air filter that install vertically in the rear of the router, and the fan tray contains six fans. Air comes in at the side of the chassis next to the air filter and leaves through the fan tray out the other side, while the power supplies draw their air from the front above the craft interface.

If a fan fails, the host subsystem adjusts the speed of the remaining fans to maintain proper cooling, and a red alarm is triggered when a fan fails. The air filter is on a calendar: Juniper says you must replace the filter every 6 months. Spare filters age on the shelf too; the shelf life of polyurethane filter varies from two years to five years depending on the storage conditions.

Dense line cards need the better tray. Juniper says the MX Series high-capacity fan trays satisfy cooling requirements for high-density DPCs and MPCs, and must be upgraded for proper cooling. The high-capacity tray is the FFANTRAY-MX480-HC, which Juniper names alongside the 2520W AC power supply, PWR-MX480-2520-AC, and the 2400W DC power supply, PWR-MX480-2400-DC. When you move to enhanced supplies, Juniper's rule is to always upgrade power supplies in adjacent slots.

In stock at Townsend

We have the PWR-MX480-2520-AC-S AC supply and the PWR-MX480-2400-DC DC supply in stock, along with an MX480 chassis for anyone building a spare. The MX480 shelf gathers the MX480 parts on our site, and the wider Juniper MX collection holds the line cards, Routing Engines and control boards for the other MX chassis.

Sources

Checked against the maker's documents on .

  1. S1Maintaining MX480 Power System ComponentsJuniper Networks · Document: MX480 Universal Routing Platform Hardware Guide · Revision: Topic page dated 2024-09-11 · Section: Replacing an MX480 AC Power Supply; Replacing an MX480 DC Power Supply; Maintaining the MX480 Power Supplies · September 11, 2024

  2. S2MX480 AC Power SystemJuniper Networks · Document: MX480 Universal Routing Platform Hardware Guide · Revision: Topic page dated 2026-01-02 · Section: MX480 AC Power Supply Description; MX480 AC Power Supply LEDs; AC Electrical Specifications; AC Power Circuit Breaker Requirements; AC Power Cord Specifications · January 2, 2026

  3. S3MX480 Power System DescriptionJuniper Networks · Document: MX480 Universal Routing Platform Hardware Guide · Revision: Topic page dated 2021-03-09 · Section: MX480 Power System Description · March 9, 2021

  4. S4Maintaining MX480 Cooling System ComponentsJuniper Networks · Document: MX480 Universal Routing Platform Hardware Guide · Revision: Topic page dated 2024-09-11 · Section: Maintaining the MX480 Air Filter; Replacing the MX480 Air Filter; Maintaining the MX480 Fan Tray; Replacing the MX480 Fan Tray · September 11, 2024

  5. S5MX480 Cooling SystemJuniper Networks · Document: MX480 Universal Routing Platform Hardware Guide · Revision: Topic page dated 2021-03-09 · Section: MX480 Cooling System Description · March 9, 2021

  6. S6Maintaining MX480 ComponentsJuniper Networks · Document: MX480 Universal Routing Platform Hardware Guide · Revision: Topic page dated 2024-09-11 · Section: MX480 Field-Replaceable Units (FRUs); Tools and Parts Required to Replace MX480 Hardware Components · September 11, 2024

  7. S7MX480 Interface Modules: MPCs and MICsJuniper Networks · Document: MX480 Universal Routing Platform Hardware Guide · Revision: Topic page dated 2025-10-06 · Section: MX480 SCB, Power Supply, and Cooling System Requirements for AS MLC · October 6, 2025

In stock now

PWR-MX480-2520-AC-S Juniper Power Supply, Refurbished, MX480 Series 2520W AC Router Power Supply

PWR-MX480-2520-AC-S

PWR-MX480-2520-AC-S Juniper Power Supply, Refurbished, MX480 Series 2520W AC Router Power Supply

In stock

$355Ships same day
PWR-MX480-2400-DC Juniper Power Supply, Refurbished, MX480/MX240 2400W DC POWER

PWR-MX480-2400-DC

PWR-MX480-2400-DC Juniper Power Supply, Refurbished, MX480/MX240 2400W DC POWER

In stock

$150Ships same day
CHAS-BP3-MX480-S Juniper Chassis, Refurbished, MX480 8U spare chassis with enhanced BP3 midplane

CHAS-BP3-MX480-S

CHAS-BP3-MX480-S Juniper Chassis, Refurbished, MX480 8U spare chassis with enhanced BP3 midplane

In stock

$2,475Ships same day
MPC10E-15C-MRATE Juniper Line Card, Refurbished, 12x 10/25/40/100GbE QSFP28 and 3x 400GbE QSFP56-DD

MPC10E-15C-MRATE

MPC10E-15C-MRATE Juniper Line Card, Refurbished, 12x 10/25/40/100GbE QSFP28 and 3x 400GbE QSFP56-DD

In stock

$26,725Ships same day

Need help planning your next move?

Tested, warrantied hardware with real availability, and cash offers for decommissioned gear. Quotes answered by a human.